5
Outdoor wall installaon
Outdoor roof installaon
A flexible installaon that opmises
the pressure drop on the inlet side.
Makes it possible to choose outlet
direcon. In the event of
condensaon problems, installaon
as illustrated is recommended. If
noise levels are the priority, it is
recommended to have the outlet
poinng straight up, with drainage
in the fan housing (for drainage see
page 3).
Note! The fan bracket must be
made on site.
An installaon that is used when
low noise levels are priorised.
The disadvantage of this
arrangement is that the fan is
located high up if the extract air
duct is high.
Note! The fan housing needs to be
drained (for drainage see page 3).
A low-level, sideways outlet
direcon is suitable in the event of
condensaon problems.
Note! The base must be made on
site due to possible snow.
Upwards outlet direcon, suitable
in the event of noise problems.
Note! Drainage is required (for
drainage see page 3).
A high-level, sideways outlet
direcon is suitable when conden-
saon is not a problem.
Note! Drainage is required (for
drainage see page 3).