8 Maintenance
Maschinenfabrik Reinhausen GmbH 2018 411800059/09 EN RS
8 Maintenance
DANGER
Electric shock!
Working on the transformer when the transformer is energized can lead to
death or serious injuries.
Switch off transformer on high and low-voltage side.
Lock transformer to prevent unintentional restart.
Ensure that everything is de-energized.
Visibly connect all transformer terminals to ground (grounding leads,
grounding disconnectors) and short circuit them.
Cover or cordon off adjacent energized parts.
DANGER
Electric shock!
Working on the on-load tap-changer when on-load tap-changer components
are energized can lead to death or serious injuries.
De-energize all auxiliary circuits, such as the tap-change supervisory de-
vice, pressure relief device, pressure monitoring device.
Make sure that everything is de-energized.
WARNING
Danger of explosion!
Explosive gases in the oil compartment of the on-load tap-changer, trans-
former, pipework system, oil conservator and at the dehydrating breather
opening can deflagrate or explode and result in severe injury or death!
Ensure that there are no ignition sources such as naked flame, hot sur-
faces or sparks (e.g. caused by the build-up of static charge) in the trans-
former's immediate surroundings and that none occur.
Do not operate any electrical devices (e.g. risk of sparks from impact
wrench).
Only use conductive and grounded hoses, pipes, and pump equipment
that are approved for flammable liquids.
NOTICE
Damage to motor-drive unit!
Damage to the motor-drive unit due to condensate in protective housing of
motor-drive unit.
Always keep protective housing of the motor-drive unit tightly closed.
In the event of operation interruptions of more than 2 weeks, connect and
operate the anti-condensation heater in the motor-drive unit. If this is not
possible, e.g. during transportation, place a sufficient amount of desiccant
in the protective housing.

Table of Contents