4 Commissioning
Maschinenfabrik Reinhausen 2013 132349487/01 EN TAPGUARD® 260
Setting communication interface
The following section describes how to configure the communication inter-
face.
Setting CIC1 card and CIC2 card
Depending on the control system protocol, you have to set the following pa-
rameters:
Parameters IEC
60870-5-
101
IEC
60870-5-
103
MODBUS
ASCII/
RTU
DNP3 ABB SPA TAP-
CON®-
trol
Communication port x x x x x x
Baud rate communication x x x x x x
Network address - - x x - x
TCP port - - x x - x
OF light on/off x x x x x -
MODBUS ASCII/RTU - - x - - -
Local SCADA address x x x x x -
SCADA master address - - - x - -
Unrequested messages - - - x - -
Repeatedly unrequested
messages
- - - x - -
Appl. confirm. time ex-
ceeded
- - - x - -
RS485 transmit delay
time
x x x x x x
Table 2: Device parameters
To set the parameters, proceed as follows:
► > Configuration > Continue > Continue >
Comm. interface 1 or Comm. interface 2 > Press until the
desired parameter is displayed.
Setting SID card
The SID card interface is used to connect the device via the IEC 61850 con-
trol system protocol. You must set the following parameters for this:
▪ Network address
▪ Network mask
▪ Gateway
▪ Time server address
▪ IED name
To set the parameters, proceed as follows:
4.5
4.5.1
4.5.2