EasyManua.ls Logo

MSA 9010 - Page 2

MSA 9010
2 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Status LEDs (red/yellow) 6 Display
2 System Failure LED (yellow) 7 Keypad
3 POWER LED(green) 8 Measured value
4 Gas Information Tag 9 Measuring units
5 Site Information Tag 10 Control Unit Status
Front Panel and Display Information
Startup
Code Description Code Description
F1.1*
Detector supply current is too high
F6.2
Externalwatchdogfailure
F1.2*
Detector supply voltage is too high
F7.1*
Digital output failure
F1.3
Possibleshortcutondetectorside
F7.2
Digital output failure
F1.4*
Defaultcongurationhasbeenloaded
F7.3
Digital output failure
F1.5*
Transmitter does not provide a constant current
F8.1
Selftestfailure
F1.6*
TransmittercosumeslesscurrentthanitissetinMenu4/P2.
F8.2
SelftestRAM1failure
F1.7
Sensorcurrentisturnedoff
F8.3
SelftestRAM2failure
F1.8
Possibleshortcutondetectorside
F8.4
SelftestFlashfailure
F5.1
ADCconvertorfailure
F8.5
Selftestcongurationfailure
F5.2
ADCBackupconvertorfailure
F8.6
SelftestCPUfailure
F5.3
ADCconvertorfailure
F8.7
Selftestclockfailure
F5.4
Sensorcurrentcannotbeset
F9.1
SettingswerechangeddueATEXmode
F5.5
Testing voltage is too low
F9.2
Factory default values were loaded
F5.6
Testing voltage is too high
F9.3
Userdefaultvalueswereloaded
F5.7
Transmitter supply voltage too high
F9.4
Factory/Userdefaultvaluescannotbeloaded
F5.8
Transmitter supply voltage too low
F9.5
Userdefaultvaluesnotsaved
F6.1
Externalwatchdogwastriggered
F9.6
Passwordnotaccepted
*Failure message must be acknowledged by operator pressing UP or ENTER key on the front panel
Error Codes
Code Description Code Description
E1 Sensorsensitivityistoolow -d1 Input signal is below limit
E2 Sensorsensitivityistoohigh EEEE Input signal is over measuring range
E3
Sensorsensitivityisreduced
(soonreplacementmustbeexpected)
LOU1* External24VDCistoolow
E4 Detectorsignalisoutofoptimalrange(>300mV) LOU2* Internal24VDCistoolow
E10 SamevalueforZEROandSPANhasbeenset LOU3* Controller supply is too high
LOU4* Internal temperature is too low
LOU5* Internal temperature is too high
Menu Access
Access Code 1
Calibration
Access Code 2*
Settingsforparticularoperatingconditions
Access Code 3
Simulationandfunctiontests
Access Code 4*
Conguration
Access Code 6*
Basic setup
Access Code 7*
Peripheralssetup
Access Code 52*
InputandOutputSetup
Access Code 53*
Default settings
Access Code 223
Passwordsetup
*AccessCode123isrequired
RefertothemanualfordetailedAccessCodefunctionsdescription.
Attheendofthestartup
procedure,the“CAL”symbolis
shortly displayed and the control
unit starts the regular operating
mode.Sensorwarmuprunson
the background during the startup
procedure.
The startup procedure can be
accelerated with the front keys:
PressEnter/Up/Downkeyto
displaynextitemimmediately.
PressESCkeytoskipthe
startup procedure
NOTE: Please contact your local MSA representative if you have a problem with the unit setup or testing.
Failure Identication Codes
www.MSAsafety.com
Schlüsselstrasse12
8645Rapperswil-Jona
Switzerland

Related product manuals