6.3.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.6
and check as shown in table 6.2
6.4 MTL5014 single-pole changeover
relay single-channel dual-output
switch/proximity detector with line
fault detection and phase reversal
The MTL5014 enables two safe-area loads to be relay-controlled by a
single hazardous-area switch or proximity detector. Phase reversal (see
3.1.3 and figure 6.8), line fault detection and slave/line fault monitoring
configurations are possible.
6.4.1 Wiring connections
See figure 6.7 for wiring connections
Note: Reactive loads must be adequately suppressed.
13
INM5000-6 Jul 2010
6.3.1 Wiring connections
See figure 6.5 for wiring connections.
6.3.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
Input line faults (open- or short-circuit) are indicated by an LED and the
non-conducting of the output. LFD is enabled/disabled by a switch
located on top of the module. Note that if the LFD facility is enabled for
switch inputs, the resistors shown in figures 6.5 and 6.6 MUST be fitted.
Table 6.2
Terminal Function
1 Input –ve
2 Input +ve
3 Earth leakage detection
10 &11 Output –ve
12 Output +ve
13 Supply –ve
14 Supply +ve
+
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
To earth
leakage
detector
SW
22kW
680W
a
b
c
+
1kW
V
d
Phase Input Output Channel Line fault
reverse Line fault switch status status LED LED
switch detection (SW) (11-12) (yellow) (red)
Normal Off a V
d
< 4V On Off
Reverse Off I
sc
= 7–9mA V
d
= V
S
Off Off
Reverse Off Open V
d
< 4V On Off
Normal On V
oc
= 7V5–9V5 V
d
= V
S
Off On
Normal On a V
d
= V
S
Off On
Normal On c V
d
< 4V On Off
Normal On b V
d
= V
S
Off Off
Terminal Function
1 Input –ve
2 Input +ve
3 Earth leakage detection
7 Normally closed (output 2)
8 Common (output 2)
9 Normally open (output 2)
10 Normally closed (output 1)
11 Common (output 1)
12 Normally open (output 1)
13 Supply –ve
14 Supply +ve
Figure 6.6: Test circuit for MTL5012
+
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
To earth
leakage
detector
22kW
680W
+
Resistors required only
for line fault detection
Figure 6.5: MTL5012 wiring diagram and connections
Hazardous area
Safe area
Figure 6.7: MTL5014 wiring diagram and connections
Safe area
Hazardous area