Chapter 6 Troubleshooting 
SCV-series Screw Compressors 
6-9 
  Trouble  Direct causes  Factors  Actions 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
vibration 
and/or 
noise of 
compressor 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
load operation at 
below 30 % of 
capacity control   
During low load operation, lubricant 
is poorly discharged. Because of 
this, the amount of oil that remains 
inside rotor mesh increases and oil 
becomes compressed. 
→Avoid continuous low load opera-
tion. 
*  Especially for light gas such as 
He and NH
3
, 10 minutes low load 
operation has a negative effect. 
  For fluorocarbons, low load 
operations of more than 30 
minutes are not recommended 
during startup 
*  Initial abnormal 
noises are 
conspicuous. 
→If this 
phenomenon 
happens, in some 
cases, 
compressor  
gets instantly 
 
is stopped, 
refrigerant is 
liquefied and 
remains in 
upstream piping. 
This is due to various factors such 
as a leak inside the liquid supply 
solenoid valve on load side, 
insufficient heat exchange 
(refrigerant evaporation) in heat 
exchanger, or liquid trapping 
caused by wrong piping in piping 
route. 
→Identify the causes (more than 
one may exist), and take 
measures. Then, perform an 
overhaul of the compressor.   
during operation 
*  Frosting on 
suction side is 
conspicuous. 
*  In many cases, 
the phenomenon 
is often 
“mist-back” 
(suction of moist 
steam) rather 
than liquid 
flow-back. 
*  To prevent this 
phenomenon, 
gas‐liquid 
separator 
(accumulator) 
can be installed. 
*  Refer to Factor 
“Insufficient 
refrigerant 
circulation 
volume” in item 
02 as well. 
supply expansion 
valve is too large. 
For temperature type expansion 
valve, inspect temperature sensitive 
cylinder and capillary tube.   
Take measures if any defects are 
found. 
For incompatible orifice due to the 
change in operating conditions, 
replace orifice. 
For electronic expansion valve, 
inspect devices on expansion valve 
opening control devices (circuit) 
such as temperature sensor, 
converter, controller (over-heating 
regulator). If any defects are found, 
replace the faulty devices. 
As with temperature type expansion 
valve, for incompatible orifice due to 
the change in operating conditions, 
replace orifice. 
unloaded operation 
to full load 
operation 
Set control parameters so that rapid 
change will not occur. 
Or, re-adjust opening of oil 
controller valve on capacity control 
increase side towards the decrease