3/15 IOM-SDTU
Installation and Operation Manual
Single Duct Terminal Units
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Page 1 of 4
Receiving Inspection
After unpacking the assembly check it for
shipping damage. If any shipping damage is
found, report it immediately to the delivering
carrier. During unpacking and installation do
not handle by the inlet velocity sensor or the
control package.
Determine Position of the
Control Enclosure
The control enclosure can be installed on
either side of the ductwork by flipping the VAV
unit over 180 degrees. Unit with mercury
contactors, pneumatic controls, and digital
controls (DDC) need to be inspected before
installing.
Important: Unit with mercury contactors is
position sensitive. As a result, before installing
unit with mercury contactors, inspect the
position of the mercury contactors in the
control enclosure. Mercury contactors must be
heading up 90 degrees vertically. If they are
heading down, unscrew the mercury contactors,
rotate 180 degrees, and reinstall them.
If unit is equipped with pneumatic controls, it
should be mounted right side up and level
within ±10 degrees of horizontal, and parallel to
the airflow. The first letter in the model number
indicates control type (P is for pneumatic). If
the unit is mounted upside down, the controller
will have to be repositioned, re-piped, and
recalibrated. Analog control units (A-analog
model number pre-fix) may be installed in any
orientation. Some Digital (DDC) controls
(D-digital model number pre-fix) are position
sensitive dependent on the airflow sensor
transducer. Check with the controls
manufacturer for verification.
Supporting the Assembly
We recommend that each terminal unit be
independently supported, especially when
accessory modules, such as coils, attenuators,
silencers or multiple outlets are present.
Hanger straps may be used and screwed
directly into the sides or bottom of the unit
casing (see Fig. 1). Alternately, a carriage
made of unistrut may be used, somtimes this is
known as a trapeze setup. Support the VAV
and any accessories separately (Fig. 2). When
requested, unit is supplied with field mounted
hanger brackets for use with hanger rod up to
3/8" (9.5) dia. Hanger brackets should be
screwed into the top of the unit casing (see Fig.
3 & 4). Use the support method prescribed for
the rectangular duct in the job specifications.
CONTROL
ENCLOSURE
INLET
OPTIONAL HANGER BRACKET
(FIELD LOCATED
& INSTALLED)
RECTANGULAR
DISSIPATIVE SILENCER
SLIP & DRIVE
CONNECTION
COIL
SECTION
COMPRESSION STRAP ON FLEXDUCT
TO ENSURE AIRTIGHT JOINT
OPTIONAL
ACCESS DOOR
CONTROL
ENCLOSURE
RECTANGULAR
DISSIPATIVE SILENCER
SLIP & DRIVE
CONNECTION
COMPRESSION STRAP ON FLEXDUCT
TO ENSURE AIRTIGHT JOINT
CONTROL
ENCLOSURE
INLET
SLIP & DRIVE
CONNECTION
COMPRESSION STRAP ON
FLEXDUCT TO ENSURE
AIRTIGHT JOINT
OPTIONAL
ACCESS DOOR
COIL
SECTION
RECTANGULAR
DISSIPATIVE
SILENCER
SLIP & DRIVE
CONNECTION
ACCESS
DOOR
VAV
SECTION
DISCHARGE
DUCT
INLET
DUCT
CONTROL
ENCLOSURE
SLIP & DRIVE
CONNECTION
OPTIONAL HANGER BRACKET
(FIELD LOCATED & INSTALLED)
METAL STRAP HANGERS
SECURED TO BUILDING STRUCTURE
INLET
5/16" OR 3/8" (8 OR 10) DIAMETER HANGER RODS
SECURED TO BUILDING STRUCTURE
MINIMUM 2 DUCT DIAMETERS
OF STRAIGHT DUCT
ON AIR TERMINAL INLET
MINIMUM 2 DUCT DIAMETERS
OF STRAIGHT DUCT
ON AIR TERMINAL INLET
MINIMUM 2 DUCT DIAMETERS
OF STRAIGHT DUCT
ON AIR TERMINAL INLET
DISCHARGE
DUCT
DISCHARGE
DUCT
DISCHARGE
DUCT
Figure 1: Support Using Hanger Straps (Shown: Model D30RW - Single Duct VAV
Terminal Unit with Hot Water Heat).
Figure 2: Support Using Unistrut and Rods (Shown: Model 3001Q - Single Duct
Terminal Unit with Dissipative Silencer).
Figure 3: Support Using Optional Supplied Hanger Brackets (Shown: Model
D30RWQ - Single Duct VAV Quiet Terminal Unit with Standard Dissipative
Silencer and Hot Water Heat).
Figure 4: Support Using Optional Supplied Hanger Brackets (Shown: Model
D30HQX - Single Duct VAV Exhaust Terminal Unit with Dissipative Silencer).
Question and Answer IconNeed help?

Do you have a question about the Nailor D30RE and is the answer not in the manual?

Summary

Receiving Inspection

Determine Position of the Control Enclosure

Supporting the Assembly

Duct Connections

Field Wiring

Control Start-up and Operation

Replacement Parts

Recommended Maintenance

Provides guidance on lubricating bearings for long-term unit performance.

SCR Fan Speed Controller (PSC Motors)

Part numbers for SCR fan speed controllers for PSC motors.

Control Start-up, Operation

Installation

Balancing Procedure

Mechanical Minimum Stop Field Setting Procedure

Pneumatic Actuator

Procedure for setting minimum stop on pneumatic actuators.

Electric Actuators

Procedure for setting minimum stop on electric actuators.

ELECTRICAL SUGGESTIONS AND REQUIREMENTS

Primary Air Damper and Fan Adjustment

Maintenance Procedures

Application charts for ECM motors

General

Receiving Inspection Checklist

Check unit for shipping damage before unwrapping packaging material.

Safety Precautions

Guidelines for qualified personnel and awareness of building utilities.

Electrical Suggestions and Requirements

Water Pipe Connections

Appendix A - MCA and MOP Calculations

Model 33 SZ • Orientations

INSTALLATION

OPERATION

NAMEPLATE LABEL

HEATER CONTROL ENCLOSURE

Heater Element Rack Replacement For Series Fan Powered Terminal Units

LED INDICATORS

SETTING AIRFLOW

Setting the Fan Airflow in the Manual Mode

Procedure to set fan airflow using manual mode and potentiometer adjustment.

Setting the Fan Airflow in the Dynamic Automation (0 - 10 VDC) Mode

Procedure to set fan airflow using a 0-10 VDC signal from a controller.

TROUBLESHOOTING IN MANUAL ADJUST MODE

TROUBLESHOOTING IN AUTO; DYNAMIC 0-10 VDC MODE

EZvav Sensors:

Mount the sensors

Step-by-step instructions for mounting the EZvav sensor to its base.

Choosing a sensor location

Rough-in preparation

Operation

Maintenance

Planning for motion sensing

Changing room set points

EZvav Controllers:

Align the damper and drive hub

Procedure to align the damper and drive hub on the VAV box.

Mount the controller to the VAV box

Instructions for mounting the EZvav controller to the VAV box.

Connect the room sensor cable

Connect the EZvav sensor to the controller using an Ethernet cable.

Connect the airflow sensors

Connect the airflow sensor to the controller using FR tubing.

Connect auxiliary equipment (optional)

Connect other VAV equipment like fans, heaters, and sensors.

Connect 24 volt power

Connect the controller to a 24 volt Class 2 transformer.

Configuration

CTE-5100 Series Thermostats:

Installation:

Electrical box mounting:

Instructions for mounting thermostats to standard electrical boxes.

CSP-5002 DAMPER CONTROLLER;ACTUATOR

ANALOG CONTROL CALIBRATION CHARTS VOLTAGE VS. AIRFLOW

CALIBRATION PROCEDURE FOR AIR VOLUME ADJUSTMENTS MADE AT THERMOSTAT

CTE - 5101 SINGLE SETPOINT THERMOSTAT

Calibration procedure for single setpoint thermostats.

CTE - 5103 DUAL SETPOINT THERMOSTAT (Heat; Cool Changeover)

Calibration for dual setpoint thermostats with heat/cool changeover.

CTE - 5104 DUAL SETPOINT THERMOSTAT

CTE - 5105 DAY; NIGHT THERMOSTAT (Night Temperature Set Back)

FAN POWERED TERMINAL UNITS

Checkout Procedure (Day; Occupied Mode)

Checkout Procedure (Night; Unoccupied Mode)

REE - 5002 Relay Module Fan with 2 Stage Reheat

TROUBLESHOOTING PROCEDURE