NAPCO Gemini C-Series Control Panel Programming Instructions--Volume 2
Page 92 Programming Instructions, Volume 2
SYSTEM OPTIONS (ADDRESS 5320 -5324, 5331 )
5322
System Options
5323
System Options
Default
Option
Default
Option
OFF
1
Opening Report only after Alarm Report
OFF
1
Auto Output Test Upon Arming
OFF
2
Closing Report only on Cond. Closing (Auto-Byp.)
ON
2
Auto-Reset after Burg Bell Timeout
OFF
3
Include Sel./Grp. Bypass in Cond. Closing Status
OFF
3
Suppress Bypass Icon when Armed
OFF
4
Status Report (Auto-Byp. Zones on Clos.)
OFF
4
RESERVED
OFF 5
RESERVED
OFF
5
Access Control on Burg Module PGM1 Output
OFF 6
RESERVED
OFF
6
Enable Burg. Bell Warning on Entry
OFF 7
Disable Auto-Unbypass on Disarming
OFF
7
Enable Managers Mode Outside Overview
OFF 8
Enable All-Zone-in-Trouble Bypass
OFF
8
Start Exit Delay after Ringback
5324
System Options
Default
Option
OFF
1
Interior 1 Normally Bypassed
OFF
2
Enable Exit-Delay Restart
OFF
3
Reset Day Zone/Trouble with Arm/Disarm Only
OFF
4
Enable Local Alarm on First Zone AND Trip
OFF 5
Disable Keypad Function-Mode Download
OFF 6
Disable Callback Download
OFF 7
Disable Answering-Machine Download
OFF 8
Disable Auto-Reset in Day Zone/Trouble
SYSTEM OPTIONS:
1. Select the desired option entering the option
number (1-8) for each digit.
2. Enter corresponding option number in address
location.
NOTE: Dark shaded data value box shows option not
available. Press U to save.
5321
System Options - Enable Day Zone/Trouble Watch
Default
Option
OFF
1
RESERVED
OFF
2
Enable Day Zone/Trouble Watch (Area 2)
OFF
3
Enable Day Zone/Trouble Watch (Area 3)
OFF
4
Enable Day Zone/Trouble Watch (Area 4)
OFF
5
Enable Day Zone/Trouble Watch (Area 5)
OFF
6
Enable Day Zone/Trouble Watch (Area 6)
OFF
7
Enable Day Zone/Trouble Watch (Area 7)
OFF
8
Enable Day Zone/Trouble Watch (Area 8)
5330
NAC System Options
Default
Option
ON
1
Class A Configuration NAC 1 / NAC 2
OFF
2
Class A Configuration NAC 3 / NAC 4
OFF
3
Supervision Disabled NAC A
OFF
4
Supervision Disabled NAC B
OFF 5
Supervision Disabled NAC C
OFF 6
Supervision Disabled NAC D
OFF 7
Enable Panel Relay Fire Trouble Relay
OFF 8
RESERVED
NAC SYSTEM OPTIONS (ADDRESS 5330, 7952)
7952
NAC System Options
Default
Option
OFF
1
Enable Multiple Ring Connection Method
OFF
2
Enable 15 Ring Connection Method
OFF
3
Enable Telephone Line 1 Fault Test
OFF
4
Enable Telephone Line 2 Fault Test
OFF 5
Enable Co NACs Off On Fire Alarm
OFF 6
Horn/Strobe Simultaneous Silence
OFF 7
Keypad 1 Always Unlocked for User Functions
OFF 8
All Keypads Unlocked for Silence, Reset and Supp.
5331
System Options
Default
Option
ON
1
WL Fire 200 Sec. Supervision
OFF
2
RESERVED
OFF
3
RESERVED
OFF
4
RESERVED
OFF 5
RESERVED
OFF 6
RESERVED
OFF 7
RESERVED
OFF 8
RESERVED
Address 5331, "WL Fire 200 Sec. Supervision": When enabled, the supervisory time for any
transmitter programmed for Area 1 (FIRE) from time selected in TIME SELECTION to 200
seconds. Note: Must use wireless fire "-2" model devices. Use Quickloader V6.4.8 or greater.