W415-0326 / 01.06.02
7
Use the GD401 periscope kit to locate the air termination
above grade. The periscope must be installed so that when
final grading is completed, the bottom air slot is located a
minimum of 12 inches above grade. The maximum allow-
able vent length depends on the fireplace, as illustrated.
FIGURES 3 a-c
FIGURE 4
TYPICAL VENT INSTALLATIONS
SPECIAL VENT INSTALLATIONS
40FT
MAX
3FT
MIN
16"
TO GRADE
MINIMUM
12"
10" MIN
24" MAX
USE GD201 PERISCOPE KIT
BELOW GRADE INSTALLATION
MAXIMUM 10FT VENT LENGTH
OF HORIZONTAL
REGARDLESS
VENT LENGTH
24" MINIMUM
12"MINIMUM
NOTE:
When terminating vertically, the restrictor
plate W500-0205 must be installed. Refer to
Restricting Vertical Vents.
PERISCOPE TERMINATION