display (DTB 01) and on the mobile app, the
notification appears: "Overcurrent". In this case, a
consumer has been activated that draws a power
that exceeds the limits allowed by the battery. We
recommend limiting the use of such a consumer to
a maximum of 1 minute.
6. Battery pole voltage above 16V. The alarm is
automatically deactivated when the voltage drops
below 15.6V. On the BUS display (DTB 01) and on the
mobile app, the notification "Battery over voltage"
appears. Check that the charger is not faulty and
that it is suitable for charging batteries with a
nominal voltage of 12V and LiFePO
4
technology.
7. Battery pole voltage below 10.5V. The voltage at the
poles is switched off for a few minutes, and then
automatically restored for a few seconds. The
purpose of this function is to protect the battery
from further discharge by keeping it switched off for
a few minutes, and at the same time to allow a
battery charger to detect it. On the BUS display (DTB
01) and on the mobile app, the following notification
appears: "Battery voltage low".
If on the NDS display (DTB 01) and on the APP, the
notification 'Battery Fault' appears, the alarm is not
reset, you must contact service.