uPASS Target | quick reference guide
4/
5
Connections
All connectors shown in this chapter are seen from the outside of the reader.
Figure 5: uPASS Target connectors
CONN.1
CONN.2
CONN.3
Pin
Function
1
RS422 TX-
2
RS422 TX+
3
RS422 RX- / RS485 B
4
RS422 RX+ / RS485 A
5
Ground
Function
Input 1 / UL
Wiegand Data 0 / Magstripe Clock
Magstripe Card loaded
Wiegand Data 1 / Magstripe Data
RDIS
Ground
Ground
Input 2 / NA
Pin
Function
1
Relay NO
2
HF Data
3
Relay NC
4
Relay COM
5
Ground
RS422 / RS485
The RS422 or RS485 communication can be used for communication with the Access Control System, configuration
settings and firmware update. Only the RS422 or the RS485 interface can be active (not both), this is determined by
SW1-2 (located near the USB port).
The maximum cable length for both interfaces is 65 meters / 213 feet. This distance can be increased by adding
termination resistors, using twisted cables and/or configuring a lower baud rate.
Wiegand / Magstripe
The Wiegand and Magstripe communication can be used for communication with to Access Control System only. The
Wiegand and Magstripe can operate with a maximum cable length of 150 meters / 500 feet.