26
NETAJET
4G USER MANUAL
4)
Check for an air pocket in the dosing booster impeller chamber (see the enclosed Dosing Booster Manual):
Open the NetaJet™ 4G sampling outlet until a stable flow, free of air-bubbles, is obtained.
5) If the original hydraulic conditions are still not restored - loosen the dosing booster's bleeding screw
and wait until a stable flow, free of air-bubbles, is obtained, then retighten the bleeding screw
(
see the enclosed Dosing Booster Manual
).
6) Check the dosing booster's impeller chamber for clogging:
If it is clogged - it should be dismantled and thoroughly cleaned (see the enclosed Dosing Booster Manual).
If after implementing all the above steps the malfunction is still not fixed - consult your Netafim
representative.
Symptoms regarding a single dosing channel
TROUBLESHOOTING
A
B
C
D
Analog dosing channel Digital dosing channel
H
G
E
F
A
H
G
E
F
D
Analog dosing valve Digital dosing valve
OPEN
Manual operation
AUTO
Controlled operation
OPEN
Manual operation
CLOSE
Controlled operation
OPEN
CLOSE
OPEN
CLOSE
OPEN
AUTO
OPEN
AUTO