47
0x04 401 uInt16 All outputs TPF [-]
0x04 402 uInt16 1st output TPF [-]
0x04 403 uInt16 2nd output TPF [-]
0x04 501 Int16 All outputs Phase shift [° *100]
0x04 502 Int16 1st output Phase shift [° *100]
0x04 503 Int16 2nd output Phase shift [° *100]
0x04 601 uInt16 All out. reverseEnergy counter - 2up.bytes [Wh]
0x04 602 uInt16 All out. reverseEnergy counter - 2lo.bytes [Wh]
0x04 603 uInt16 1st out. reverseEnergy counter - 2up.bytes [Wh]
0x04 604 uInt16 1st out. reverseEnergy counter - 2lo.bytes [Wh]
0x04 605 uInt16 2nd out. reverseEnergy counter - 2up.bytes [Wh]
0x04 606 uInt16 2nd out. reverseEnergy counter - 2lo.bytes [Wh]
0x04 803 uInt16 1st digital input S0 counter - 2 upper bytes
0x04 804 uInt16 1st digital input S0 counter - 2 lower bytes
0x04 805 uInt16 2nd digital input S0 counter - 2 upper bytes
0x04 806 uInt16 2nd digital input S0 counter - 2 lower bytes
0x04 1001 uInt16 All outputs energy NR counter - 2 upper bytes [Wh]
0x04 1002 uInt16 All outputs energy NR counter - 2 lower bytes [Wh]
0x04 1003 uInt16 1st output energy NR counter - 2 upper bytes [Wh]
0x04 1004 uInt16 1st output energy NR counter - 2 lower bytes [Wh]
0x04 1005 uInt16 2nd output energy NR counter - 2 upper bytes [Wh]
0x04 1006 uInt16 2nd output energy NR counter - 2 lower bytes [Wh]
0x04 1101 uInt16 All out. reverseEnergy NR counter - 2up.bytes [Wh]
0x04 1102 uInt16 All out. reverseEnergy NR counter - 2lo.bytes [Wh]
0x04 1103 uInt16 1st out. reverseEnergy NR counter - 2up.bytes [Wh]
0x04 1104 uInt16 1st out. reverseEnergy NR counter - 2lo.bytes [Wh]
0x04 1105 uInt16 2nd out. reverseEnergy NR counter - 2up.bytes [Wh]
0x04 1106 uInt16 2nd out. reverseEnergy NR counter - 2lo.bytes [Wh]
0x05 102 0/1 Turn On/Off 1st output (Write)
0x05 103 0/1 Turn On/Off 2nd output
0x05 104 0/1 Turn On/Off 3rd output
0x05 105 0/1 Turn On/Off 4th output
0x06 102 uInt16 Set action to 1st output
0x06 103 uInt16 Set action to 2nd output
0x06 104 uInt16 Set action to 3rd output
0x06 105 uInt16 Set action to 4th output
0x06 202 uInt16 Set "Short" delay of 1st output [s*10]
0x06 203 uInt16 Set "Short" delay of 2nd output [s*10]
0x06 204 uInt16 Set "Short" delay of 3rd output [s*10]
0x06 205 uInt16 Set "Short" delay of 4th output [s*10]

Other manuals for Netio PowerBOX 4KE

Related product manuals