For indoor and outdoor applications.
Only for cables NF C 33-226, UTE C 33-223, NF C 33-223 & HN 33-S-23 [Part 1],
NF C 33-220 (HN 33-S-22) with graphite coating screen [Part 2],
NF C 33-220 (HN 33-S-22) with extruded semi-conductive screen [Part 3].
In case the ambient temperature is less then 0°C, it could be necessary to warm up the
sealing mastic and tape.
CAUTION : Read instructions thoroughly and completely prior to beginning installation.
Installation Instructions Separable Elbow Connector - CENELEC interface type A
(K)200LR
Up to 24 kV
Check if the diameter over cable core insulation is in accordance with
the cable reducer range as indicated in table below:
Cable reducer size
(see marking inside cable reducer)
200CA-12
200CA-16
13.0
17.5
21.0
25.0
Dia. over core insulation (mm)
min max
This product should be installed only by competent personnel trained in good safety practices involving
high voltage electrical equipment. These instructions are not intended as a substitute for adequate
training or experience in such safety practices. These instructions do not attempt to provide for every
possible contingency. Failure to follow these instructions could result in damage to the product and
serious or fatal injury. IMPORTANT : Cable and associated apparatus must be de-energised, locked
out, and tagged prior to product installation.
Page 1/9
IS97082-ENG - 200LR/G-MT345
15 January 2018 - Revision 0 - Supersedes edition of 3 June 2016
IS97082-ENG - 200LR/G-MT345 - Revision 0
Question and Answer IconNeed help?

Do you have a question about the Nexans Euromold K200LR and is the answer not in the manual?

Summary

Part 1: Installation for NF C 33-226 Cables

Cable Preparation and Screen Earthing (Part 1)

Steps for preparing cables NF C 33-226, UTE C 33-223 for installation.

Watersealing Application

Procedure for applying water sealing mastic and adhesive tape to the cable.

Cable Reducer Installation

Lubricating and fitting the cable reducer onto the prepared cable end.

Contact Tightening

Tightening the conductor contact using a hex key until bolt heads shear.

Connector Mounting on Cable

Sliding the connector housing onto the cable reducer and securing the pin contact.

Connector Mounting on Bushing

Connecting the elbow connector to the equipment bushing and earthing lead.

Part 2: Installation for Graphite Coating Screen Cables

Cable Preparation and Screen Earthing (Part 2)

Steps for preparing NF C 33-220 cables with graphite coating screen.

Part 3: Installation for Extruded Semi-Conductive Screen Cables

Cable Preparation and Screen Earthing (Part 3)

Steps for preparing NF C 33-220 cables with extruded semi-conductive screen.