49NIBE BA-SVM 10-200
Alarm
no.
Alarm text on the
display
Cause Heat pump action. May be due to
39 Sensor fault
EQ1–BT64
Sensor BT64 not con-
nected, defective.
Shuts off cooling, Closes
shunt (QN18) for cooling.
See troubleshooting page
28.
52 The temperature
limiter has
tripped
Temperature limiter
has tripped
Internal electrical addition is
blocked.
56 Incorrect
serialnumber
Serial number and
program do not match
The compressor stops, all
relay outputs are set to 0 V
Check serial number
57 Incorrect
program
Serial number and
program do not match
Compressor blocked. All
relay outputs are set to 0 V.
70 Communication
fault with PCA
input EB15
Communication with
the input card missing
for 60 secs.
Blocking the relevant com-
pressor.
Calculated flow temperature
is set to min supply line.
See troubleshooting on
page 29.
71 Communication
fault with PCA
base-AA2
Communication with
the base card missing
for 15 secs.
Compressor (EB101)
blocked.
See troubleshooting on
page 30
73-95 Existing commu-
nication fault with
”accessory”.
Communication with
the accessory card
missing for 15 secs.
Accessory is blocked. Check communica-
tion cables
Check the setting of
the dipswitch.
96-99 Existing commu-
nication fault with
”room unit”.
Communication with
room unit zone 1-4
missing for 60 secs.
Accessory is blocked. Check communica-
tion cables
206 Com. error Acc -
QZ1
Temporary commu-
nication fault HW
comfort.
Accessory blocked. Check fuses, voltag-
es to the accessory
card.
Check that the com-
munication cables are
correctly connected.
Check the setting of
the dipswitch.
220 High pressure
alarm.
See relevant manual. Compressor blocked. See relevant manual.
221 Low pressure
alarm.
See relevant manual. Compressor blocked. See relevant manual.
222 Motor protection
alarm.
See relevant manual. Compressor blocked. See relevant manual.
223 comm.error from
heatpump
See relevant manual. Compressor blocked. See relevant manual.
224 Fan alarm. See relevant manual. Compressor blocked. See relevant manual.
225 supply/return
temp sensors
mixed up.
See relevant manual. Compressor blocked. See relevant manual.
227 Sensor fault. See relevant manual. Compressor blocked. See relevant manual.
228 Defrosting fault. See relevant manual. Compressor blocked. See relevant manual.
229 Short operating
time.
See relevant manual. Compressor blocked. See relevant manual.
Section 7 | Troubleshooting

Questions and Answers: