CopperVPBS 300
277litreVolume (no dedicated solar storage volume)
2litreVolume, charge coil
0.8litreVolume, solar coil
24litreVolume, expansion vessel
12.4kWhHeat content at 50 °C
470litreEquivalent amount of hot water (40 °C)
5
280litrePrimary coil capacity, domestic water (60 °C to 40 °C)
282litreSolar coil capacity, domestic water (60 °C to 40 °C)
29minutesHeating time charge coil (10 °C to 60 °C)
4
1h52mh/mHeating time solar coil (10 °C to 60 °C)
6
85°CMax operating temperature
3/0.3bar/MPaMax pressure, primary side
5.5/0.55bar/MPaMax pressure, water heater
3/0.3bar/MPaMaximum pressure, solar coil
16/1.6bar/MPaMax water supply pressure
6/0.6bar/MPaMax design pressure
3.5/0.35bar/MPaExp. vessle, tap water, charge pressure
6/0.6bar/MPaExpansion relief valve, setting
85°CMax temperature, heating fluid
7/0.7bar/MPaMax operating pressure, T&P-valve
95°CMax operating temperature, T&P-valve
F1145-6,8,10,12, F2030-7,9, F2040-8,12,16,
F1155-6,12,16, F2120-8,12,16
Compatible NIBE heat pumps
1
1800mmHeight
1950mmRequired ceiling height
2
600mmWidth
600mmDepth
137kgNet weight
416kgGross weight
081 082Part No.
1
For ground source heat pumps, this recommendation applies to max. 10 °C brine temperature and 53 °C in the tank.
2
With the feet removed, the required ceiling height is approx. 1930 mm.
4
At primary flow temperature 80 °C and primary flow 1025 l/h.
5
At incoming temperatures 10 °C and hot water draining of 30 l/min.
6
At primary flow temperature 80 °C and primary flow 278 l/h.
Tested according to standard EN 12897:2016.
Energy labelling
NIBESupplier
VPBS 300 CuVPB 300 RModel
CC
Energy efficiency class
9588WHeat loss
277282lVolume
23Chapter 4 | Technical dataVPB/VPBS

Other manuals for Nibe VPB Series