Pressthe and buttons.
Setthevalueto“F-3”
usingthe and 
buttons.
Pressthe and buttons.
Pressthebuttonuntil
theSW1LEDflashes.
Setthevalueto“60.0”
usingthe and 
buttons.
Pressthe buttonformore
thanonesecondtoreturn
totheOperationsMode.
Pressthe buttonfor
morethanonesecond
toreturntotheOperations
Mode.
Setthevalueofthefirst
digitto“7”usingthe
 and buttons.
Pressthe button
untiltheSW2LED
underthefirstdigit
flashes.
Intheoperationsmode,
pressthe and 
buttonssimultaneously
toentertheInitial
SettingsMode.
4
PressureSettingsMode
SwitchOutputSetting
Theswitchoutputsettingisdeterminedbythevalueofthefirstdigit:theredSW2LEDshouldbeflashingduringthesetting.
Therearefouroperationmodes.Theseareshowninthediagramsbelow.
Note1.IntheSeparateMode,setting1correspondstoSW1,andSetting2correspondstoSW2.
Note2.IntheWindowComparatorMode,theminimumvalueforSW1andSW2correspondstoSetting1andthe
    maximumvaluecorrespondstoSetting2.
Valueselected
kPa
+/− SW1 SW2
kPa
+/− SW1 SW2
+/− SW1 SW2
Pressthe and buttons
simultaneouslytoenter
thePressureSettingsMode.
(TheSW1LEDflashes.)
TheLEDofanitemflashes
whenselectedusingthebutton.
Pressthe buttontoselect
betweenswitchoutput1setting
(SW1),switchoutput2setting
(SW2),orthehysteresissetting.
Setthevalue
usingthe
andbuttons.
Pressthe buttonfor
morethanonesecond
toreturntotheOperations
Mode.
Output
Mode
Operation
1
2
3
4
5
6
7
8
SW1output
Separate
H
L
A
B
H
L
A
B
Windowcomparator
Note1
Setting1
Note2
Minimum
:Setting1
Maximum:Setting2
Minimum
:Setting1
Maximum:Setting2
Note1
Setting2
Note2
Separate
Windowcomparator
SW2output
kPa
+/− SW1 SW2
kPa
+/− SW1 SW2
 Anexampleofsettingthevalue“7”forthemodeshowninthediagram.
■WindowComparatorMode
ON
ON
OFF
OFF
SW1
SW2
Setting
value1
Setting
value2
Hysteresis Hysteresis
SeparateMode WindowComparatorMode
Hysteresissetting Switchoutput2
setting
Switchoutput1
setting
kPa
+/− SW1 SW2
kPa
+/− SW1 SW2
kPa
+/− SW1 SW2
kPa
+/− SW1 SW2
Low High
(Hoperation)
OFF
ON
ーPr Pr
H
H
P1:SW1 P2:SW2
ON
OFF
ーPr Pr
H
H
P1:SW1 P2:SW2
(Loperation)
(Aoperation)
OFF
ON ON
ーPr Pr
H H
P1 P2
P1 P2
(Boperation)
OFF OFF
ON
ーPr Pr
H H
F-0ResponseTime=5ms
F-1ResponseTime=25ms
F-2ResponseTime=250ms
F-3ResponseTime=2.5s
Digitalfiltersetting
+/− SW1 SW2
P1≦P2 or P1≧P2 P1≦P22H
Note:+50%F.S.issetpriortodelivery.
Anexampleofsetting60kPaforswitchoutput1(SW1LEDisflashing)with102R.
Tosetswitchoutput1theSW1LEDshouldbeflashing.(Tosetswitchoutput2theSW2LEDshouldbeflashing.)
Note:20digitsissetpriortodelivery.
Anexampleofsettingahysteresisvalueof8.0kPawiththe102R(kPa).
SwitchOutputSetting
HysteresisSetting
DigitalFilterSetting
Tosethysteresisthe“”LEDshouldbeflashing.
TosetDigitalFilterallLEDshouldbenotflashing.
Anexampleofsetting2.5sresponsetimebyDigitalFilter.
Pressthe buttonuntil
theLEDflashes.
Setthevalueto“8.0”
usingthe and 
buttons.
Pressthe buttonfor
morethanonesecondto
returntotheOperations
Mode.
Note:“F-0”issetpriortodelivery.
Pressthe buttonuntil
allLEDdonotflashe.
Pressthe buttonfor
morethanonesecondto
returntotheOperations
Mode.
Pressthe and buttons