3. PROGRAMMING
The default setting of the analog control is as follows:
- operation: 0 -10V
- min. is set to the lowest possible intensity
- max. is set to the highest possible intensity
You can modify these default settings. The programming mode comprises
the following 3 sections: 'input' (3.A), 'min' (3.B) and ‘max’ (3.C).
Proceed as follows:
Press the programming button for >2s to enter the analog control’s
programming mode. This mode always starts in ‘input’. Repeatedly
press the programming button briefly to run through the 3 sections:
'input', 'min', 'max'. A LED indicates the selected section of the
programming mode.
To save the settings, exit the programming mode: press the programming
button for >2s.
If nothing happens for 3min, the programming mode is automatically
exited and the settings are not saved.
Note: If the analog control is in programming mode, the panic function
does NOT work.
A. Setting ‘input’ control mode
The ‘input’ section is used to select the control mode. To select one
of the 3 control modes, proceed as follows (see also the following
diagram):