EasyManua.ls Logo

Nittan EVCA-P - Page 5

Default Icon
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DW1500110 Rev.K1
Sep 18 2015
5
6.2.1 Avoidance of unwanted alarms
Smoke detectors can be affected by various environmental factors (other than smoke), which may accidentally activate
the detectors. It is necessary to consider where smoke detectors should be installed in order to minimize unwanted
alarms. Listed below are some common sources of unwanted alarms to be considered when locating smoke detectors.
Steam and moisture
Chemical fumes
Cooking equipment
Welding, cutting, and industrial processes
Dust or lint
Engine exhaust
Vibration or shock
Excessive airflow
Lightning
Radio frequency radiation
The smoke detector signals a dirty sensor trouble to the control panel when it reaches the preset limit. The dirty
sensor trouble indicates the detector is in need of servicing.
6.2.2 Spacing of Smoke Detectors
The recommended spacing of spot type smoke detector is maximum 9.1 m (30 ft.), based on the detector installation
on a smooth ceiling at 3 m (10 ft.) high. All points on the ceiling shall have a detector within a distance equal to or less
than 0.7 times the nominal 9.1 m (30 ft.) spacing.
Note: It is recommended that smoke detectors be installed on S = 9.1 m (30 ft.) centers, on smooth ceilings. Refer to
NFPA 72 National Fire Alarm Code for additional information on spacing adjustments.
Spot-type smoke detectors must be located on the ceiling or, if on a sidewall, between the ceiling and 30 cm (12 in.)
down from the ceiling to the top of the detector.

Related product manuals