5.5 Event ID descripons
Event ID Descripon of Cause
E01
Bus Start Fail: DC-DC converter or bus sensing circuit
failed.
E02 Bus Volt High: DC-DC converter failed.
E03 Bus Volt Low: DC-DC converter failed.
E04 Bus Unbalanced: DC-DC converter failed.
E06 INV Start Fail: Inverter circuit failed.
E07
INV Volt High: Inverter circuit or output voltage sensing
circuit failed.
E08
INV Volt Low: The load may be too heavy or inverter
circuit failed.
E09 INV Short: The inverter circuit failed.
E11
Bat Volt High: The external baery module connecon is
wrong, or the charger failed.
E12 Bat bad: Baeries failed.
E14 Over Load: UPS is overloaded.
E18
Fan Fail: The venlaon hole has been covered, or the
fans can’t work.
E19
Over Temperature: High ambient temperature, or the
venlaon hole has been covered.
A62 Bat low: Baery voltage low.
A66 EPO O: Missing the EPO connecon
A68
High Temperature: High ambient temperature, or the
venlaon hole has been covered. This is shown only
when start up UPS.
Seng
item
Congure
Submenu
Available
Sengs
Default
Seng
LCD Display
003
ECO
Mode*
[0%]
(Disable)
[10%]
[15%]
(Enable)
0%
004
Bypass
Mode**
[DIS]
(Disable)
[ENA]
(Enable)
Enable
005
Converter
Mode
[DIS]
(Disable)
[ENA]
(Enable)
Disable
*) When operang in ECO Mode, the eciency of UPS is higher than that in online mode,
but transfer me should not be 0ms
**) When operang in Converter Mode, the frequency of output should be always 50Hz
or 60Hz, but load capacity will be derated by 40%.
*) This funcon would be set as 0% when Converter Mode is enabled.
**) UPS has no bypass when Converter Mode is enabled.