20 21
Troubleshoong
6
Problem Possible Cause Soluon
Warning
O/P Overload
Your equipment requires
more power than the UPS
can provide. If the UPS is
in Line Mode then it will
transfer to Bypass Mode;
if the UPS is in Baery
Mode it will shut down.
Shut o non-essenal
equipment. If this solves
the overload problem,
the UPS will transfer to
normal operaon.
Baery Mode
UPS is operang on
baery power.
Save your data and
perform a controlled-
shutdown.
Baery Low
UPS is operang on
baery power and will be
shung down soon due
to extremely low baery
voltage.
UPS will restart
automacally when
acceptable ulity power
returns.
BAT
Disconnected/
Baery Replace
Missing baery power.
Check baery connector
when use baery
packages.
UPS has failed in Baery
Test.
Contact technical
support to replace the
baery.
Charger Failure Charger has failed.
1.
Shut down UPS and
turn o AC input.
2.
Contact your dealer
for repair.
EPO OFF
Missing the EPO
connecon.
Check the EPO
connecon.
Fault
Over
Temperature
High ambient
temperature.
1.
Shut down UPS.
Restart UPS to Check
the fan for operaon
and if the venlaon
hole has been covered
2.
Contact your dealer
for repair.
Output Short Output short circuit.
1.
Shut down UPS
2.
Your aached
equipment may have
problems, please
remove them and
check again.
High O/P V
Output voltage is too
high.
1.
Shut down UPS
2.
Contact your dealer
for repair.
Low O/P V Output voltage is too low.
Bus Fault
Internal DC bus voltage is
too high or too low.
Other
Startup fail
High temperature, or fan
fail, or baery low, or
EPO o.
1.
Restart UPS and press
the “ESC” buon to
view the warning
event. Then refer to
the soluon for the
warning.
2.
Contact your dealer
for repair.