Rdg1 = 0
Out1 = 4 (mA)
Rdg2 = 100
Out2 = 20 (mA)
Out/Limit
Limiting the analog output between Out1 and
Out2. E.g. if Out1=4 and Out2=20, the
analog output will not go under 4 mA nor
over 20 mA.
However, if the channel that the output
follows indicates fault, the output will always
exceed the range between Out1…Out2 by
20% (the output will be Out1+1.2*(Out2-
Out1)); however it can't go above 22 mA or
11 V.
Monitor menu
Out
The analog output in mA or V. The analog
signal will be electrically limited 0-11 V and
0-22 mA but this value does not obey that
limit.
The analog output can be manually steered
to test the external systems. Give a Lock
command to this item, and enter desired
values in mA or V. To return to the normal
operation, give a Free command.