P734
Phase W current
(W phase current)
S
0.0 ... 999.9 A Displays the actual W phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
Pos: 59 8 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P7 00-P7 99/Par amet er P735 – Drehz ahl Dr ehg eb er [ SK 2 xxE , SK 2 xxE-FD S] @ 2\mod_1347348492128_388.docx @ 44440 @ @ 1
P735
Encoder speed
(encoder speed)
S
-9999 ... 9999 rpm Displays the actual rotation speed supplied by the incremental encoder.
correctly set.
Pos: 59 9 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 700- P799 /Par amet er P736 – Zwischenkreisspannung @ 0\mod_1328174969216_388.docx @ 13192 @ @ 1
P736
D.c. link voltage
(DC link voltage)
0 ... 1000 V DC Displays the actual link voltage.
Pos: 60 0 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P7 00-P7 99/Par amet er P736 – Zwisc hen kreis sp ann ung _Erg änz ung Anz eige klei n er Wert bei 24V_ G erät en [ SK 2 xxE] @ 5\mod_1397202429585_388.docx @ 126240 @ @ 1
Information
Display of untypical value
In devices with a separate 24 V supply, a small, non-typical value is displayed if no mains
voltage is present (e.g.: with 1~ 230 V devices: P736 ≈ 4 V). This value results from internal
measuring and testing routines, and is dependent upon measuring errors, offsets and signal
noise, for example.
Pos: 60 1 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 700- P799 /Par amet er P737 – A ktu elle Aus las tung Br ems wider s tan d @ 0 \mod_1328175007763_388.docx @ 13215 @ @ 1
P737
Usage rate brakeres.
(Actual brake resistor usage rate)
0 ... 1000 % This parameter provides information about the actual degree of modulation of the brake chopper
or the current utilisation of the braking resistor in generator mode.
If parameters P556 and P557 are correctly set, the utilisation related to P557, the resistor power,
is displayed.
If only P556 is correctly set (P557=0), the degree of modulation of the brake chopper is displayed.
Here, 100 means that the brake resistor is fully switched. On the other hand, 0 means that the
brake chopper is not active at present.
If P556 = 0 and P557 = 0, this parameter also provides information about the degree of
modulation of the brake chopper in the FI.
Pos: 60 2 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/P7 00-P7 99/P aram eter P738 – Aktuelle Ausl astung Motor [ SK 1x0E, SK 2xxE, S K 2xxE-FD S] @ 2\mod_1346932207014_388.docx @ 43560 @ @ 1
P738 [-01]
[-02]
Motor usage rate
(current motor usage rate)
0 ... 1000 % Shows the actual motor load. Basis for calculation is the motor data P203. The actually recorded
current is related to the nominal motor current.
[-01] = in relation to I
N
(P203) of the motor
[-02] = in relation to I
2
t monitoring, "in relation to I
2
t monitoring" (P535)
Pos: 60 3 /Allgemein/Allgemeingültige Module/---------Seiten umbruc h komp akt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1