Operation | 50
(User Defined Settings Continued)
Ground FI
When on the contactor will be
disengaged whenever the drain
valve is activated to prevent
current leakage to the drain.
(Default = Off).
Fill Stop
When activated during a fill cycle
the fill valve will be turned off
when current equals 95% of
demand to prevent overshooting
the demand. (Default = Off).
Adapting
Reserved for future development.
Do not adjust. (Default = Off)
Idle Mode
Configures operation when no
demand is present. Idle Only =
no action. 3 Day Drain = drain
cylinder after 72 hours. Keep
Warm = keep cylinder warm by
periodically engaging contactor.
(Default = 3 Day Drain).
3DD Force
When On the humidifier will drain
the contents of the cylinder every
3 days regardless of demand or
idle condition. It can improve
performance for water conditions
with sediment or other
contaminants. (Default = Off)
Drain Mode
Configures when a corrective
drain will be performed in case
the software detects excess
current. Fixed ED = drain at
115% of full capacity. Float ED =
drain at 115% of current demand.
(Default = Fixed ED).
User Defined Settings
Drain Cool : On
Dfactor : 1.0
Foam Mode : Off
Rapid Modu : Off
ShortCyc : Off
Ground FI : Off
Menu Set
Ground FI : Off
Ground FI
Off
Off
On
Menu Set
Off