EasyManuals Logo

Nortec NHPC User Manual

Default Icon
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
Operation | 50
(User Defined Settings Continued)
Ground FI
When on the contactor will be
disengaged whenever the drain
valve is activated to prevent
current leakage to the drain.
(Default = Off).
Fill Stop
When activated during a fill cycle
the fill valve will be turned off
when current equals 95% of
demand to prevent overshooting
the demand. (Default = Off).
Adapting
Reserved for future development.
Do not adjust. (Default = Off)
Idle Mode
Configures operation when no
demand is present. Idle Only =
no action. 3 Day Drain = drain
cylinder after 72 hours. Keep
Warm = keep cylinder warm by
periodically engaging contactor.
(Default = 3 Day Drain).
3DD Force
When On the humidifier will drain
the contents of the cylinder every
3 days regardless of demand or
idle condition. It can improve
performance for water conditions
with sediment or other
contaminants. (Default = Off)
Drain Mode
Configures when a corrective
drain will be performed in case
the software detects excess
current. Fixed ED = drain at
115% of full capacity. Float ED =
drain at 115% of current demand.
(Default = Fixed ED).
User Defined Settings
Drain Cool : On
Dfactor : 1.0
Foam Mode : Off
Rapid Modu : Off
ShortCyc : Off
Ground FI : Off
Menu Set
Ground FI : Off
Ground FI
Off
Off
On
Menu Set
Off

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nortec NHPC and is the answer not in the manual?

Nortec NHPC Specifications

General IconGeneral
BrandNortec
ModelNHPC
CategoryHumidifier
LanguageEnglish

Related product manuals