18
B64VM
A-CABINET
COOLING AIRFLOW
A/B SWITCH SETTING
0 = OFF, 1 = ON
COOL SWITCH SETTING
0 = OFF, 1 = ON
AIRFLOW
(CFM)
5 6 7 8
0 0 0 0 0 525
0 0 0 0 1 560
0 0 0 1 0 600
0 0 0 1 1 625
0 0 1 0 0 700
0 0 1 0 1 750
0 0 1 1 0 800
0 0 1 1 1 850
0 1 0 0 0 875
0 1 0 0 1 890
0 1 0 1 0 930
0 1 0 1 1 950
0 1 1 0 0 1000
0 1 1 0 1 1050
0 1 1 1 0 1125
0 1 1 1 1 1200
B64VM
B-CABINET
COOLING AIRFLOW
A/B SWITCH SETTING
0 = OFF, 1 = ON
COOL SWITCH SETTING
0 = OFF, 1 = ON
AIRFLOW
(CFM)
5 6 7 8
1 0 0 0 0 525
1 0 0 0 1 560
1 0 0 1 0 600
1 0 0 1 1 650
1 0 1 0 0 700
1 0 1 0 1 750
1 0 1 1 0 800
1 0 1 1 1 850
1 1 0 0 0 875
1 1 0 0 1 950
1 1 0 1 0 1050
1 1 0 1 1 1150
1 1 1 0 0 1250
1 1 1 0 1 1350
1 1 1 1 0 1400
1 1 1 1 1 1600
B64VM
C-CABINET
COOLING AIRFLOW
A/B SWITCH SETTING
(* = EITHER 0 OR 1)
COOL SWITCH SETTING
0 = OFF, 1 = ON
AIRFLOW
(CFM)
5 6 7 8
* 0 0 0 0 1100
* 0 0 0 1 1200
* 0 0 1 0 1250
* 0 0 1 1 1300
* 0 1 0 0 1350
* 0 1 0 1 1400
* 0 1 1 0 1450
* 0 1 1 1 1500
* 1 0 0 0 1550
* 1 0 0 1 1600
* 1 0 1 0 1650
* 1 0 1 1 1700
* 1 1 0 0 1750
* 1 1 0 1 1800
* 1 1 1 0 1900
* 1 1 1 1 2000
Table 8. B64VM (VSHE) Airflow Data
HEATING AIRFLOW
A/B SWITCH SETTING
0 = OFF, 1 = ON
HEATER KIT
INSTALLED
(KW)
AIRFLOW
(CFM)
0 0 600
0 5 800
0 8 1000
0 10 1000
0 15 1300
0 20 n/a
0 25 n/a
HEATING AIRFLOW
A/B SWITCH SETTING
0 = OFF, 1 = ON
HEATER KIT
INSTALLED
(KW)
AIRFLOW
(CFM)
1 0 700
1 5 900
1 8 1100
1 10 1100
1 15 1300
1 20 1500
1 25 n/a
HEATING AIRFLOW
A/B SWITCH SETTING
(* = EITHER 0 OR 1)
HEATER KIT
INSTALLED
(KW)
AIRFLOW
(CFM)
* 0 800
* 5 1000
* 8 1200
* 10 1200
* 15 1400
* 20 1600
* 25 1800
NOTES:
• Airflow values listed are for 240V operation. For 208V
operation, multiply A & B cabinet values by .95; for
C-cabinet values mulitply by .90
• When matched with two-stage outdoor units the
airflow on low (Y1 or W1) input only will be 70% of
the values shown in this table.