DC Inverter U-match Series Floor Ceiling Type Unit
When the height d
ifference between
the indoor unit and outdoor unit is more
than 10m (32feet), an oil bend should be
made
for every 6m (20 feet).
î
4.5 Drain Pipe Installation
(1). 4.5.1 Precautions
(1). Keep piping as short as possible and slope it downwards at a gradient of at
least 1/100 so that air may not remain trapped inside the pipe.
(2). Keep pipe size equal to or larger than that of the connecting pipe.
(3). Install the drain pipe as shown and guard against condensation. Improperly
installed piping could lead to leaks.
Fig. 4.19
(4). Connect the drain hose (Fig. 4.20).
Fig. 4.20