UDS-4 Installation and user manual PAGE - 11
UDS-4_manu M--203.1-UDS4N-ENG Rev A.1 NOTIFIER ITALIA
Access Level 2. Allows to silence the siren output after the generation of the Release Condition.
If the siren output has been silenced, it is possible to reset it by pressing the button again and
always with the same access level. This behaviour applies also in case of a fault (open circuit or
short circuit). In case the siren output is excluded, this command has no effect.
Following the silencing of the siren output, the button is coloured yellow to indicate this. After manually silencing the
siren, the siren can be reset automatically if the shutdown phases so require and the button colouring is restored.
Access Level 2 .
Allows the restoration of fault, activation and release conditions.
There is a constraint on the ability to perform a Reset: when the UDS is in the Trigger Condition
and subsequent Conditions, the Reset is inhibited for a time, in minutes, equal to that set in the
"CONF -> Delays -> Reset Delay" parameter.
The countdown is not suspended when the emergency extension input is activated.