EasyManua.ls Logo

Notifier SFP-400B - Power

Notifier SFP-400B
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SFP-400B 15124:G1 06/24/97
18
1 2 3 4 5 6
+24VU +24VR +24VNR
+ - + - + -
This output is not suitable for power-
ing devices requiring filtered, regu-
lated DC power.
The combined current draws from the Resettable and Non-Resettable outputs
cannot exceed 200 mA.
TB2
Trouble Relay
One Form-C dry trouble contact is provided in the basic panel for controlling supplementary devices. It
is rated 2 amps at 30 VDC, 0.5 amps at 30 VAC (resistive) and will silence when trouble condition is cleared.
See below for terminal location.
Note: The alarm and trouble Form-C dry contact relays must be power limited relays. Any Form-C dry contact
relay that may be used must be wired from one of the 24V power limited terminals as shown in the figure below
or a comparable UL listed power limited power supply.
Figure 3.5-1: Diagram of Power Terminals
AC Power
Primary power required for the SFP-400B panel is 120 VAC, 50/60 Hz, 1.2 amps and primary power
required for the SFP-400BE panel is 220/240 VAC, 50 Hz, 0.6 amps. Overcurrent protection for this circuit
must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use #14 AWG or
larger wire with 600 volt rating.
Unregulated Power
24 VDC power for inductive-type
devices such as door holders
can be connected to TB2 termi-
nals 1(+) and 2 (-).
4-Wire Smoke Detector Power
24 VDC filtered, regulated, reset-
table power for 4-wire smoke de-
tectors can be obtained from TB2
Terminals 3 (+) and 4 (-).
Non-resettable Power
24 VDC filtered, regulated, non-
resettable power can be drawn
from TB2 Terminals 5 (+) and 6 (-).
3.5 Power
CAUTION: Several different sources of power can be connected to this panel. Disconnect
all sources of power before servicing. The panel and associated equipment may be
damaged by removing and/or inserting cards, modules, or interconnecting cables while
this unit is energized.
1 2 3 4 5 6
Alarm Trouble
1 2 3 4 5 6
TB2
+ - + - + -
+24VU +24VR +24VNR
TB4
ALARM TROUBLE
NO NC C NO NC C
- - -
- - -
- - -
or or
Figure 3.4-2: Alarm / Trouble Coils and Contacts

Related product manuals