6 SEQUENCES
Sequence number Sequence
Maximum No. Steps per controller for
1 sta
e 3 sta
e 6 sta
e
S 00 1:1:1:1:1:1 1 3 6
S 01 1:1:2:2:2:2 1 4 10
S 02 1:2:2:2:2:2 1 5 11
S 03 1:2:3:3:3:3 1 6 15
S 04 1:2:3:4:4:4 1 6 18
S 05 1:2:4:4:4:4 1 7 19
S 06 1:2:3:6:6:6 1 6 24
S 07 1:2:4:8:8:8 1 7 31
When each capacitor stage has the same value, e.g. 50, 50, 50, 50 kvar, sequence S 00 should be
selected.
For systems with different step ratios, choose the appropriate sequence.
For example, for 50, 100, 100, 100 kvar, choose sequence S 02.