PIA-982027-AIR 85-td-EN | www.ochsner.com 41
Data table
Control circuit
AIR 85 C14A
Rated voltage range V ~220-240 L1/N /PE
Rated current A 6,3
Fuse protection 1x C13A 1p
HEAT SINK SYSTEM AIR 85 C14A
Heat transfer medium Water
Max. heat transfer medium op. pressure bar 10
Temperature differential (WNA) K 5
Flow rate (WNA) m³/h 10,9
Residual head (WNA) mbar 818
Flow meter FM 50 x 2” fem. kvs 40 external
3-way switching module (DHW) DN50 (2”), kvs 40 external
Circulation pump Stratos Para 65/1-12 external
Condenser type (WNA) Plate heat exchanger
Condenser material (WNA) Stainless steel 1.4301
PERFORMANCE FIGURES
Weight (excl. packaging) kg 295
A7/W35
AIR 85 C14A
Heating output (EN14511) kW 68,10
Power consumption (EN14511) kW 13,97
Coefficient of performance COP (EN14511) 4,87
A2/W35
AIR 85 C14A
Heating output (EN14511) kW 50,17
Power consumption (EN14511) kW 12,95
Coefficient of performance COP (EN14511) 3,87
A-7/W35
AIR 85 C14A
Heating output (EN14511) kW 47, 90
Power consumption (EN14511) kW 13,32
Coefficient of performance COP (EN14511) 3,60
A2/W55
AIR 85 C14A
Heating output (EN14825) kW 51,92
Power consumption (EN14825) kW 18,80
Coefficient of performance COP (EN14825) 2,76
A35/W7
AIR 85 C14A
Cooling capacity (EN14825) kW 38,80
Power consumption (EN14825) kW 15,50
Energy efficiency ratio EER (EN14825) 2,50
ENERGY EFFICIENCY (AVERAGE CLI-
MATE ZONE)
AIR 85 C14A
at max. flow temperature (heating) °C 35 55
Energy efficiency class (D to A+++) A++ A++
P rated kW 54 56
Efficiency ETAs % 169,6 136,7
SCOP 4,32 3,49
at min. flow temperature (cooling) °C 18 7
SEER 3,6 3,26

Table of Contents

Related product manuals