5 Maintenance
25
Adjust the displayed value using the
potentiometer (Figure 24, rep.1).
Example
- CO sensor.
- Scale 0-300 ppm.
- Standard gas concentration: 100
ppm.
- Reading: 533 mV.
Shut off the calibration gas injection.
Withdraw the gas injection pipe.
Then wait and check that the scale
has returned to zero. Otherwise,
repeat the entire procedure.
Switch the maintenance on/off switch
to the MES (measure) position
(ref. 1).