EasyManuals Logo

OMEGA AIR RDP Series User Manual

OMEGA AIR RDP Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25
● The inlet air is too hot. Establish normal operating conditions.
● The inlet pressure is too low. Establish normal operating conditions.
● The flow of inlet air is higher than the flow of the dryer - reduce flow - establish
normal operating conditions.
● The condenser is dirty - clean it.
● The condenser fan does not work.
● Condensate has not been drained from the dryer.
● The hot gas bypass valve is not properly set up - contact an engineer in the field
of refrigeration.
● Leakage has occurred in the cooling circuit - contact a specialist in the field of
refrigeration.
The dewpoint is too
low
● Fan always on - PV pressure switch is defective - replace it.
● Ambient temperature is too low - establish nominal operating conditions.
● The hot gas bypass valve is not properly set up - contact an engineer in the field
of refrigeration.
Excessive pressure
drop in the dryer
● Condensate has not been drained from the dryer.
● Dew point is too low - the condensate is frozen and blocks the air flow.
● Check the dampening of the pipe connections.
.....................................................................................................
The condensate was
not drained from
the dryer
● Check the electrical installation.
● Dew point is too low - the condensate is frozen and blocks the air flow.
● The compressed air pressure is too low and the condensate is not removed -
establish normal operating conditions.
● The electronic condensate drain is not working properly.
The dryer
continuously drains
the condensate
● The electronic condensate separator is dirty.
There's water in the
pipeline.
The dryer does not start.
If it is installed - Unprepared air flows through the bypass conduit - close the
bypass conduit.
● The dryer does not discharge condensate.
● Dew point is too high.
High compressor
outlet temperature
● Check which of the following caused the activation:
1. Overload heat - set normal operating conditions.
2. The temperature of the input air is too high - establish normal operating
conditions.
3. The ambient temperature is too high, or the ventilation of the room is too low
- ensure adequate ventilation.
4. The condenser is dirty.
5. The fan does not work.
6. The hot gas bypass valve is not properly set up - contact the engineer in the
field of refrigeration.
7. Coolant is leaking - consult with an engineer in the field of refrigeration.
- Reset the thermal switch by pressing the button on the thermal switch itself -
check the proper operation of the dryer.
- TS thermal switch is defective - replace it.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the OMEGA AIR RDP Series and is the answer not in the manual?

OMEGA AIR RDP Series Specifications

General IconGeneral
BrandOMEGA AIR
ModelRDP Series
CategoryDryer
LanguageEnglish

Related product manuals