16
negative v alue allo w ed is -199.9, -19.99, or -1.999.
Note:Note:
Note:Note:
Note: InPC is reset to zero when
the input type is changed, or when decimal position is changed in T/C or RT D
ranges. Changing decimal position in current or v oltage r anges will not reset InPC.
FiLtFiLt
FiLtFiLt
FiLt Digital Filter : Select
OFF OFF
OFF OFF
OFF,
1 1
1 1
1 to
99 99
99 99
99 . In some cases the time constant of the sensor,
or noise could cause the display to jump enough to be unreadable. A setting of 2
is usually sufficient to pro vide enough filter ing for most cases, (2 represents
approximately a 1 second time constant). When the 0.1 degree resolution is
selected this should be increased to 4. If this v alue is set too high, controllability will
suffer.
SECONDSECOND
SECONDSECOND
SECOND
ARAR
ARAR
AR
Y MENU (cont'd)Y MENU (cont'd)
Y MENU (cont'd)Y MENU (cont'd)
Y MENU (cont'd)
LPbrLPbr
LPbrLPbr
LPbr Loop Break Protection: Select
OFFOFF
OFFOFF
OFF
,,
,,
,
1 1
1 1
1 to
9999 9999
9999 9999
9999 seconds. If, dur ing oper ation, the
output is minim um (0%) or maximum (100%), and the input moves less than 5°F
(3°C) or 5 counts over the time set f or LPbr, the
LOOP bAdLOOP bAd
LOOP bAdLOOP bAd
LOOP bAd message will appear.
This condition can also be routed to an Alar m Condition if alar ms are present and
tur ned On (see ALbr in the secure menu). The loop break error can be reset by
pressing the
ENTER ENTER
ENTER ENTER
ENTER key when at the LPbr menu item. The
INDEXINDEX
INDEXINDEX
INDEX &
ENTERENTER
ENTERENTER
ENTER keys
m ay also be used.
POL Process Output Low (936): Select -450°F, -260°C, or -1999 counts to 50 degrees or counts
less than POH.
POH Process Output High (936): Select from 50 degrees or counts greater than POL to
+9990°F, +5530°C, or 9990 counts. A voltage output is scalable from 0 to 10 VDC that
represents the Process Variable. To properly scale the output, the values for POL and
POH must be calculated. The simplest example is an output of 0 to 10 VDC from 0 to 200°.
In this example POL=0 and POH=200. To Calculate POL and POH for other ranges use
the following:
K = (Highest desired temperature - Lowest desired temperature) /
(Maximum desired voltage - Minimum desired voltage)
POH = ((10 - Maximum desired voltage) * K) + Highest desired temperature
POL = ((Minimum desired voltage - 0) * K) - Lowest desired temperature
LOrE Local / Remote Status (992): Select LOC or rE. When LOC is selected, the host computer
is advised not to send remote commands. When rE is selected, CFLt=2, and nAt is set
> 0, if the control is not accessed by the host computer in the time set in nAt, the control
will revert to the CFSP.
CFSP Communications Fail Set Point (992): Set to desired value.
Addr Control Address (992): Set from 1 to FF. This number (hexadecimal, base 16) must match
the address number used by the host computer. Viewed only in this menu.