EasyManua.ls Logo

Omega CND3 Series - Specialized Control and Tuning; FUZZY Control Mode; Multiple PID Sets and Tuning

Omega CND3 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
limit of input)*(Remote input value - lower limit of Remote input)/( higher limit of Remote input - lower limit of Remote input) –
Remote lower limit of input)
Set parameter
to in Initial Setting Mode
Note: This option is only available when a Remote board is inserted. If the Remote type is of analog current, the JP in the
Remote board must be shorted (using a short cap). If the Remote type is of analog voltage, ensure the JP is open.
Remote type setting: Set type of the Remote input (including analog current 0~20 m A,4~20m A; analog voltage 0~5V, 1~5V,
0~10V)Set Remote input type by parameter
in Initial Setting Mode
Remote positive/negative slope setting: Set corresponding value of Y position by parameter
inInitial Setting
Mode, e.g.: xYxx (Y can be 0 or 1; 0: positive; 1: negative).
Remote compensation adjustment: input corresponding lower limit of analog signal at the Remote end, set Remote
compensation adjustment by parameter
inRegulation Mode
Remote gain adjustment: input corresponding upper limit of analog signal at the Remote end, set Remote compensation
adjustment by parameter
inRegulation Mode
Remote lower limit: Setting Remote lower limit by parameter
inRegulation Mode
Remote higher limit: Setting Remote higher limit by pa
rameter
inRegulation Mode
How to setting current input
Short the Jumper on Remote board.
Normal Input (Factory Setting) Current Input (4 ~ 20mA, 0 ~ 20mA)
Control Mode Setting
There are 4 control modes; ON-OFF, PID, FUZZY and MANUAL.
ON-OFF Mode: For heating output, the output is off when input is greater than the setting value; output is on when input is smaller
than (setting value – adjustment sensitivity setting value). For cooling output, the output is on when the input is greater than
(setting value + adjustment sensitivity setting value); output is off when input is smaller than the setting value. If one of 2 outputs is
set for heating and the other for cooling, a non-action zone can be set as follows.
Set p
aramet
er
to in Initial Setting Mode
Set adjustment sensitivity: Set adjustment sensitivity by parameterRegulation Mode to
(Output 1),
(output 2)
Setting of DeadBand of both o
utputs: Set DeadBand by parameter
in Regulation Mode
DeadBand
Heating sensitivity
adjustment
Heating
Cooling
Set value
(Output ON-OFF control of both actions)
Cooling sensitivity
adjustment
Remote board
Jumper

Other manuals for Omega CND3 Series

Related product manuals