14
or C (Cooling)
Set output %: in parameter Operation Mode, PV screen displays “oUt‘x’”, ‘x’ is 1 (output 1) or 2 (output 2)
FUZZY Mode: This comprises 2 parts: PID parameters and Fuzzy exclusive parameters. Since Fuzzy control is calculated based
on P.I.D values of PID control, the user must first set P.I.D parameters or perform auto tuning (AT) to produce these parameters. In
addition, Fuzzy control includes the following 2 exclusive parameters.
a Fuzzy Gain Setting: altering this value will directly affect the calculation of Fuzzy gain. Increasing this value will directly
enhance the Fuzzy control; decreasing this value will weaken the Fuzzy control. It is recommended that this value shall be
decreased for systems with slow reaction to heating/cooling. This value may be increased for systems with quick reaction to
heating/ cooling.
b Set Fuzzy DeadBand: The effective bandwidth of Fuzzy control, when PV value enters into the range of SV-FZDB
<PV<SV+FZDB, Fuzzy control will stop calculation. I.e., when the PV is within this temperature range, its Fuzzy control is
fixed.
Set parameter
to in Initial Setting Mode
Set Fuzzy Gain: Set value of Fuzzy Gain by para
meter
in Regulation Mode.
Set Fuzzy DeadBand: Set value of Fuzzy DeadBand by
parameter in Regulation Mode.
Setting of multiple PID sets
When PID contro
l is selected, the
sy
stem provides 6 sets (PID 0~5) PID parameter sets (P, I, D and IOF parameter) to be selected by the
user. In general conditions, one set of PID (P0) is adequate. For different setting values (SV), when the same PID value is not adequate
to control the precision, the user may set up multiple sets of PID parameters for the system to automatically switch-over to an applicable
PID set.
Set only one PID set:
Set parameter
to 0 (PID 0, the first set) inRegulation Mode, set parameter to ON; at this time, the System starts to
Auto Fine-tune the PID value. During the calculation, AT LED lights up in the display panel. When the PV value generates 2 curves of
temperature oscillation based on the SV value, the AT process is completed and the AT LED in the panel goes out. The calculated PID
parameters are displayed in
, , , and , of which their content can be revised by the user.
Automatic switching-over Multiple PID sets:
Set p
arameter
to 0 (PID 0, the first set) inRegulation Mode, set the required SV value (e.g. 100 degree), set parameter
as ON; on completion of auto fine-tuning, the system fills in parameters =100, , , and
automatically, their content can b
e revised by the user.
Set p
arameter
to 1 (PID 1, the second set), set the required SV value (e.g. 150 degree), set parameter as ON; on
completion of auto fine-tuning, the system fills in parameters
=150, , , and automatically.
Set parameter
to AUTO, System will verify on its own whether the current SV value is closer to parameter or ,
and load the corresponding PID set automatically. E.g., if SV=110, system will load
parameters. If SV=140, system will load
parameters.
If more SV groups are required, PID2~PID5 can be set up with the same sequence as described above.
Tune Function
This machine provides 2 tuning methods (Auto_Tuning and Self_Tuning) for automatic generation of PID parameters (only applicable
when control mode is set to PID control).
Auto_Tuning: by full output of heating or cooling, temperature is allowed to oscillate up and down. Attain parameters of the
magnitude and period, calculate P, I, D, IOF parameters; in addition, save the temperature setting value for performing AT, for the
use of PID control. After Auto_Tuning, PID control will be carried out automatically.
Set parameter
to in Initial Setting Mode
AT setting: Set paramete
r
to in Regulation Mode
Self_Tuning: B
y full output of heating or cooling, max. slope of temperature alteration and system delay can be attained from the
Temperature-Time Curve, and P, I, D, IOF parameters can be calculated. Self tuning can be carried out in RUN mode and in STOP
mode. In the RUN mode, PID parameters are allowed to be updated when the machine is running; in the STOP mode, PID
parameters for the SV value can be atta
ined.
Set
paramete
r
to inInitial Setting Mode
ST Setting: set paramete
r
to in Regulation Mode
Set Reverse Output
output 1 reverse setting: Set a value corresponding to Y position by parameter in Initial Setting Mode, such as xxxY (Y
can be 0 or 1; 0: forward; 1: reverse)

Other manuals for Omega CND3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega CND3 Series and is the answer not in the manual?

Omega CND3 Series Specifications

General IconGeneral
BrandOmega
ModelCND3 Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals