40
RESET SETUP SUBMENU:
Press
d
33) Display flashes 1
st
digit of the previous I
REST
Reset value.
Press
b
&
c
34) Press
b
and
c
buttons to enter a new “Reset” value.
Press
d
35) Display shows
STRD
stored message momentarily and then
advances to
RATE
only, if it was changed, otherwise press
a
to
advance to
RATE
Rate Setup Submenu.
Reset unit is in seconds 0-3999.
RATE SETUP SUBMENU:
Press
d
36) Display flashes 1
st
digit of previous D
RATE
Rate value.
Press
b
&
c
37) Press
b
and
c
buttons to enter a new
RATE
value.
Press
d
38) Display shows
STRD
stored message momentarily and then
advances to the
CYCL
only, if it was changed, otherwise press
a
to advance to
CYCL
Cycle Time submenu for RTD and
Thermocouple types.
Rate unit is in seconds 000.0-399.9.
If the Output 1 is Analog Option the display skips to Damping
Factor.
CYCLE TIME SUBMENU:
Press
d
39) Display flashes 1
st
digit of the previous
CYCL
Cycle Time
value.
Press
b
&
c
40) Press
b
and
c
buttons to enter a new “Cycle Time” value.
(1 to 199 seconds)
Press
d
41) Display shows
STRD
stored message momentarily and then
advances to
DPNG
only, if it was changed, otherwise press
a
to
advance to
DPNG
Damping Factor Submenu.
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).