2.4 Troubleshooting by error code
Indoor unit error
2.4.1 E1 (IDU) Communication failure between indoor and outdoor unit
Description: the indoor unit didn’t receive feedback from outdoor unit within 1 minute.
Possible reason:
Bad connection of communication wire
Fault indoor or outdoor unit PCB
Troubleshooting and repair:
a) Check if the wiring connection between outdoor and indoor unit is loose.
b) Power off and then repower on the unit after 3 minutes. If error code disappear, problem is solved.
If not, go to next step.
c) Measure the DC voltage between P and N on back of the main PCB with multi meter.
2.4.2 E2, E3, E4 (IDU) temperature sensor fault
Description: the sampling voltage is lower than 0.06V or higher than 4.94V.
Possible reason:
Open circuit or short circuit of relevant port.
Faulty temperature sensor