7
Primary / secondary over-current protection
High discharge temperature protection
High condenser temperature protection
IDU anti-frosting protection
High IPM temperature protection
Outdoor unit fan motor stall protection
High evaporator temperature protection
DC bus low voltage protection
DC bus high voltage protection
MCE fault / sync / compressor start fault
Phase sequence error protection
Frequency limitation because of voltage
Frequency limitation because of evaporator temperature
Frequency limitation because of condenser temperature
Frequency limitation because of discharge temperature
Frequency limitation because of high IPM temperature
Frequency limitation because of current
2.4 Spot check
⚫ Method 1: After powering on 5s, long press the button in indoor unit PCB for 5s, to enter spot
check. And then short press this button to read more parameters.
⚫ Method 2: After powering on, press “up & down swing” and “left & right swing” button alternately
5 times within 10 seconds to enter spot check. Press “up & down swing” and “left & right swing”
button to read more parameters.
⚫ Spot check table: