Parameter No. Function name Data
Default da-
ta
Unit
3005Hex-3EHex
Input Terminal [AI1] Function
Selection
21: PID feed forward - -
Related function
Output Terminal [DO1] ON Delay Time
(3051Hex-0AHex)
Output T
erminal [DO1] OFF Delay T
ime
(3051Hex-0BHex)
Output Terminal [ROA, ROB] ON Delay Time
(3051Hex-0EHex)
Output Terminal [ROA, ROB] OFF Delay Time
(3051Hex-0FHex)
*1. It can be referenced or set only from the communications function or Sysmac Studio.
*2. The OFF delay of the Under sleep mode of PID control (44: PID-STP) terminal becomes the time obtained
by adding 0.1 s to Output T
erminal[DO1] OFF Delay T
ime (3051Hex-0BHex) and Output Terminal [ROA,
ROB] ON Delay Time (3051Hex-0FHex).
PID Control Function Selection
PID control is enabled by setting other than 0 to PID Control Function Selection (300EHex-02Hex).
PID Control Function Selection (300EHex-02Hex) = “1: Process normal operation,” “2: Process in-
verse operation”
If the PID process control is performed and PID calculation results are negative, the frequency refer-
ence to the inverter is limited at 0 Hz.
PID Control Function Selection (300EHex-02Hex) = “4: Process normal operation, opposite opera-
tion available,” “5: Process inverse operation, opposite operation available”
If the PID process control is performed and PID calculation results are negative, an opposite opera-
tion can be performed for the inverter. PID Control PID Output Variable Range for Process Control
(301FHex-15Hex) is disabled.
PID Control Function Selection (300EHex-02Hex) = “3: Dancer”
PID dancer control is performed. Opposite operation can be done for dancer control.
Schematic block diagram of PID process control
When PID Control Function Selection (300EHex-02Hex) = “1,” “2,” “4,” “5”
+
+
+
-
Manual speed command
PID Process Command
(300EHex-03Hex)
PID Feedback
(301FHex-14Hex)
Feedforward
PID controller
Upper Limit
(300EHex-13Hex)
Lower Limit
(300EHex-14Hex)
Frequency
Reference
Schematic block diagram of PID dancer control
When PID Control Function Selection (300EHex-02Hex) = “3”
8 Other Functions
8-112
M1 Series EtherCAT Type User’s Manual (I670)

Table of Contents