Bias = 0%, Bias base point = 0% Bias ≠ 0%, Bias base point ≠ 0%
PID process command
100%
Gain
0%
B point
100%
Analog
input
Gain
base point
-100%
-100%
PID process command
100%
Gain
Bias
0
%
B point
A point
100%
Analog
input
Bias base
point
-100%
Gain
base point
PID command by communication (300EHex-03Hex = 4)
Communication parameter (3002Hex-0EHex): T
ransmission data 20000d/100% PID command
PID Control Feedback Selection (301FHex-14Hex)
301FHex-14Hex = 0: Analog input
If “0: Analog input” is selected for PID Control Feedback Selection (301FHex-14Hex), allocate “5:
PID feedback value” to Input T
erminal [AI1] Function Selection (3005Hex-3EHex). The analog input
value is internally controlled as 0% to 100%. For details on analog input, refer to 8-3-1
Analog Input
(Function Selection) on page 8-32.
When analog input is applied to PID feedback, the following gains, biases, filters and offsets are appli-
cable.
Input ter-
minal
Input range
Bias Gain Polarity
selection
(Range
selec-
tion)
Filter Offset
Bias
Base
point
Gain
Base
point
AI1
0 to +10V,
-10 to +10V
3006Hex-
38Hex
3006Hex-
39Hex
3006Hex-
21Hex
3006Hex-
23Hex
3006Hex-
24Hex
3006Hex-
22Hex
3006Hex-
20Hex
301FHex-14Hex = 3: Pulse train input
If “3: Pulse train input” is set to PID Control Feedback Selection (301FHex-14Hex), the inverter cap-
tures a value converted into a percentage with the maximum frequency as 100% where the pulse
correction factor (3024Hex-07Hex/3024Hex-08Hex) is multiplied with the frequency value [kP/s] of
the captured pulse train input.
8 Other Functions
8-116
M1 Series EtherCAT Type User’s Manual (I670)