Model
Maxi-
mum
appli-
cable
motor
ca-
paci-
ty
[kW]
Recommended wire size [mm2]
Inverter output (U, V, W)
HHD mode HND mode
HHD mode HND mode
Allowable tempera-
ture (Note 1)
Cur-
rent
value
[A]
Allowable tempera-
ture (Note 1)
Cur-
rent
value
[A]
60°C 75°C 90°C 60°C 75°C 90°C
- 3G3M1-
A2037-ECT
5.5 - - - - 2.0 2.0 2.0 19.6
3G3M1-
A2055-ECT
- 3.5 2.0 2.0 25.0 - - - -
3G3M1-
A2075-ECT
3G3M1-
A2055-ECT
7.5 5.5 3.5 2.0 33.0 3.5 3.5 2.0 30.0
3G3M1-
A21
10-ECT
3G3M1-
A2075-ECT
11 8.0 5.5 3.5 47.0 5.5 5.5 3.5 40.0
3G3M1-
A2150-ECT
3G3M1-
A2110-ECT
15
14.0 8.0 5.5 60.0 14.0 8.0 5.5 56.0
3G3M1-
A2185-ECT
3G3M1-
A2150-ECT
18.5 22.0 14.0 8.0 76.0 14.0 14.0 8.0 69.0
- 3G3M1-
A2185-ECT
22 22.0 14.0 14.0 90.0 22.0 14.0 14.0 88.0
Model
Maxi-
mum
appli-
cable
motor
ca-
paci-
ty
[kW]
Recommended wire size
[mm2]
DC reactor connection (P1,
P(+))
HHD mode HND mode
Allowable tempera-
ture (Note 1)
Cur-
rent
value
[A]
60°C 75°C 90°C
3G3M1-A2001-ECT - 0.1 2.0 2.0 2.0 0.7
3G3M1-A2002-ECT 3G3M1-A2001-ECT 0.2 2.0 2.0 2.0 1.1
- 3G3M1-A2002-ECT 0.4 2.0 2.0 2.0 2.0
3G3M1-A2004-ECT - 2.0 2.0 2.0 2.0
- 3G3M1-A2004-ECT 0.75 2.0 2.0 2.0 3.7
3G3M1-A2007-ECT - 2.0 2.0 2.0 3.7
- 3G3M1-A2007-ECT 1.1 2.0 2.0 2.0 5.3
3G3M1-A2015-ECT - 1.5 2.0 2.0 2.0 7.0
- 3G3M1-A2015-ECT 2.2 2.0 2.0 2.0 10.2
3G3M1-A2022-ECT - 2.0 2.0 2.0 10.2
- 3G3M1-A2022-ECT 3 2.0 2.0 2.0 14.3
3G3M1-A2037-ECT - 3.7 2.0 2.0 2.0 17.1
- 3G3M1-A2037-ECT 5.5 3.5 2.0 2.0 24.4
3G3M1-A2055-ECT - 3.5 2.0 2.0 25.8
3G3M1-A2075-ECT 3G3M1-A2055-ECT 7.5 5.5 3.5 3.5 35.3
3G3M1-A2110-ECT 3G3M1-A2075-ECT 11 14.0 5.5 5.5 51.7
3G3M1-A2150-ECT 3G3M1-A2110-ECT 15 14.0 14.0 8.0 70.5
3G3M1-A2185-ECT 3G3M1-A2150-ECT 18.5 22.0 14.0 14.0 87.0