EasyManua.ls Logo

Omron 3G3M1-A4007-ECT - Page 183

Omron 3G3M1-A4007-ECT
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
No.
Function name Monitor or data range
Default
data
Setting
during
RUN
Unit
M58 Rotor Angle Monitor
0.0 to 359.9º
0 - deg
M59 Motor Electronic Thermal Monitor
0 to 100%
0 - %
M61
Inverter Internal Air Temperature
Monitor
-3276.83276.7
0 - degC
M62 Fin Temperature Monitor
-3276.83276.7
0 - degC
M63 Load Factor Monitor
-327.68 to 327.67
0 - %
M64 Motor Output Monitor
-327.68 to 327.67 % of rated
power
0 - %
M65 Motor Output Monitor on Alarm
-32768 to 32767
0 - -
M66 Speed Detection Monitor
-32768 to 32767
0 - -
M67
Transmission Error Transaction
Code for RS485 Port
1: Improper FC (Non-existent
parameter block specified)
[R
TU]
2: Improper address (Non-ex-
istent parameter number
specified) [R
TU]
3: Improper data (Range error)
[R
TU]
7: NAK (Link priority, no right,
write disabled) [RTU]
71: Checksum error, CRC er-
ror
72: Parity error
73: Framing error, overrun er-
ror, buffer full
0 - -
4 Parameter List
4-17
M1 Series Standard Type User's Manual (I669)
4-1 List of Monitors by Group
4
4-1-1 Parameter M (Monitor 1)

Table of Contents

Related product manuals