Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
E65
Reference Loss De-
tection Operation Se-
lection
0: Decelerate to stop
20 to 120 %: Continuous oper-
ation frequency ratio
999: Disable
32767
Availa-
ble
%
page
5-27
E76
Main Circuit DC Volt-
age Low-voltage De-
tection Level
200 to 400V (200Vseries)
400 to 800V (400Vseries)
235
Availa-
ble
V
page
7-106
E78
Overtorque/Undertor-
que Detection Level at
Forward Power Run-
ning
0 to 300 %
100
Availa-
ble
%
page
6-85
E79
Torque detection 1 De-
tection Timer
0.01 to 600.00 s
10
Availa-
ble
s
page
6-85
E80
Overtorque/Undertor-
que Detection Level
at Reverse Regenera-
tion
0 to 300 %
100
Availa-
ble
%
page
6-85
E98
Input Terminal [DI6]
Function Selection
0 to 188 normally-open input,
1000 to 1188 normally-close
input
98 -
-
page
7-26
E99
Input Terminal [DI7]
Function Selection
0 to 188 normally-open input,
1000 to 1188 normally-close
input
99 -
-
page
7-26
E102
2nd RUN Command
Selection
0: Operator
1: Terminal command FW or
RV
2: Operator (Forward direc-
tion)
3: Operator (Reverse direc-
tion)
4: RS-485 communication
5: Fieldbus (Reserved)
2
- -
page
5-25
4 Parameter List
4-91
M1 Series Standard Type User's Manual (I669)
4-2 List of Parameters by Group
4
4-2-2 Parameter E (Terminal Functions)