Acceleration times or deceleration
times set at (1) to (10)
(1) Acceleration time: E10
(2) Acceleration time: F07
(3) Deceleration time: E15
(4) Acceleration time: E14
(5) Acceleration time: E12
(6) Deceleration time: E11
(7) Acceleration time: E10
(8) Acceleration time: E14
(9) Deceleration time: E11
(10) Deceleration time: F08
STG1 terminal
STG2 terminal
STG4 terminal
Time
Forward
Reverse
TU terminal
TO terminal
RUN command
0.1s
100s 65.5s60.0s
C10
C06
C11
C09
C05
C07
C08
0
55.0s 50.0s 72.0s 35.0s
0.1s
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Output frequency (motor speed)
Timed operation
• With the timed operation function, operation is performed for a preset time and is stopped when the
timer value reaches 0.
• Operation is performed by timed operation when “3: Timed operation” is selected at Pattern Opera-
tion / T
imed Operation Mode Selection (C21).
• When operation is stopped during timed operation, timed operation can be stopped.
• The following shows the procedure for setting timed operation.
1. Set “3: Timed operation” to Pattern Operation / Timed Operation Mode Selection (C21) and “13”
to Operator Display Selection during Run (E43).
2. Set the timer time (time unit: seconds) by the
/ keys while viewing the timer value on the
LED monitor.
3. When the RUN command is input and operation is started, the timer time is counted down. After
the timer time elapses, the motor stops. (Timed operation is enabled also when the LED monitor
displays a value other than the timer value.)
Additional Information
When operation is performed on the FW terminal, and LED monitor display are displayed
alternately when a deceleration stop is made after timed operation. When the FW terminal is set
to OFF, the display returns to the LED monitor display.
5 Basic Settings
5-38