EasyManua.ls Logo

Omron C200H-RM201 - Appendix B Specifications; Common Characteristics

Omron C200H-RM201
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
105
Appendix B
Specifications
General Ratings
Conform to C-series ratings.
Characteristics
Common Characteristics
Communication Two-line, half-duplex
Synchronization Start-stop
Transmission lines 2-conductor (VCTF 0.75 mm recommended.)
Interface RS-485
Transmission speed 187.5 kbps
Transmission distance 200 m (total length per Master)
C500 Remote I/O Master Unit (C500-RM201)
Power consumption 300 mA max. at 5 V
Weight 500 g max.
Diagnostic functions Transmission error checks
BCC and reversed transmission verification
CPU Unit error monitoring
Transmission line short check
C500 Remote I/O Slave Unit (C500-RT201)
Power consumption 500 mA max. at 5 V
Weight 500 g max.
RUN Output OMRON G6B relay (closed during operation)
Contact capacity: 2 A max. at 250 VAC or 24 VDC (cos φ = 1)
Diagnostic functions Transmission error checks
BCC and reversed transmission verification
CPU Unit error monitoring
C200H Remote I/O Master Unit (C200H-RM201)
Power consumption 200 mA max. at 5 V
Weight 350 g max.
Diagnostic functions Transmission error checks
CPU Unit error monitoring
Transmission line short check