105
Appendix B
Specifications
General Ratings
Conform to C-series ratings.
Characteristics
Common Characteristics
Communication Two-line, half-duplex
Synchronization Start-stop
Transmission lines 2-conductor (VCTF 0.75 mm recommended.)
Interface RS-485
Transmission speed 187.5 kbps
Transmission distance 200 m (total length per Master)
C500 Remote I/O Master Unit (C500-RM201)
Power consumption 300 mA max. at 5 V
Weight 500 g max.
Diagnostic functions Transmission error checks
BCC and reversed transmission verification
CPU Unit error monitoring
Transmission line short check
C500 Remote I/O Slave Unit (C500-RT201)
Power consumption 500 mA max. at 5 V
Weight 500 g max.
RUN Output OMRON G6B relay (closed during operation)
Contact capacity: 2 A max. at 250 VAC or 24 VDC (cos φ = 1)
Diagnostic functions Transmission error checks
BCC and reversed transmission verification
CPU Unit error monitoring
C200H Remote I/O Master Unit (C200H-RM201)
Power consumption 200 mA max. at 5 V
Weight 350 g max.
Diagnostic functions Transmission error checks
CPU Unit error monitoring
Transmission line short check