Specifications Appendix B
106
C200H Remote I/O Slave Units
--- C200H-RT201 C200H-RT202
Power supply voltage 100/110 or 200/240 VAC (switchable)
50/60 Hz
24 VDC
Allowable fluctuations in supply volt-
age.
85 to 132 or 170 to 264 V
AC 20.4 to 26.4 VDC
DC output terminal 24 VDC +10%/–20%, 0.3 A max. None
Power consumption 100 VA max. 80 W max.
Weight 1.3 kg max. 1.3 kg max.
RUN Output Closed during operation
Contact capacity:
2 A max. at 250 VAC (cos
φ = 1)
0.5 A max. at 250 VAC (cos
φ = 0.4)
2 A max. at 24 VDC
Power output capacity 3 A max. at 5 VDC (actual output to I/O Units: 2.7 A max.)
Number of transmission words 10 per Slave
Remote Terminals
Power consumption** 200 mA input/500 mA output max. at 24 VDC
250 mA input/800 mA output max. at 12 VDC
Weight 250 g max.
RUN Output G6B relay (closed during operation)
Contact capacity:
2 A max. at 250 VAC or 24 VDC (cos
φ = 1)
Diagnostic functions Transmission error checks BCC and reversed transmission verification
CPU Unit error monitoring
**Power consumption is given with all Remote Terminal and I/O Block points ON.