CS/CJ Series HOST Link Driver
GP-Pro EX Device/PLC Connection Manual
14
Setting of External Device
For communication settings of INNER board, open [I/O Table] of the ladder software first. Then, select [INNER
Board Soft Switch] from the menu displayed by right-clicking [CS**-CPU**] (CPU of the External Device to
set) and set as below.
Notes
Do not set the duplicate node address in the same network address group.
Setup Items Settings
Line Speed 19200
Parameter 1,7,2,E
Mode Default (HOST Link)
Send Delay Time 0
CS Control None
Unit No. Option
Source Network Address
*1
*1 Parameter used when you access beyond network. Set in the routing table of "CX-Net Network Configuration".
Please refer to the manual of the External Device for more details.
Option
Node Address Setting Rotary Switch
*2
*2 Parameter used when you access beyond network. Set with the rotary switch on the front of the Controller Link
unit used for access beyond network.
Option