CS/CJ Series HOST Link Driver  
GP-Pro EX Device/PLC Connection Manual
14
 Setting of External Device
For communication settings of INNER board, open [I/O Table] of the ladder software first. Then, select [INNER 
Board Soft Switch] from the menu displayed by right-clicking [CS**-CPU**] (CPU of the External Device to 
set) and set as below.
 Notes
• Do not set the duplicate node address in the same network address group.
Setup Items Settings
Line Speed 19200
Parameter 1,7,2,E
Mode Default (HOST Link)
Send Delay Time 0
CS Control None
Unit No. Option
Source Network Address
*1
*1 Parameter used when you access beyond network. Set in the routing table of "CX-Net Network Configuration".         
Please refer to the manual of the External Device for more details.
Option
Node Address Setting Rotary Switch
*2
*2 Parameter used when you access beyond network. Set with the rotary switch on the front of the Controller Link      
unit used for access beyond network. 
Option