♦Changing model from CQM1H to CJ2M.
As shown on the below figure, select NewPLC1[CQM1H] and right-click or double click it to change the
PLC model. Please set the CPU model to the Device Type.
The error report might be displayed if there are instructions which cannot be converted.
Please correct and modify the program using support software function or manually, and execute program
check. If errors are detected by the program check, please correct them referring to the error report.
Right-click and
select
“Change” or
double-click.
♦Checking program
Check whether there is problem in the ladder program which was converted from the CQM1H series for
CJ2M series.
Program check
There are 2 types of program check; automatic check on the CX-Programmer and check conducted by
users. CX-Programmer checks the program when “Change model” is executed and the ledder program is
converted.
• Automatic program check on the CX-Programmer
Timing of program check Description
When PLC model is changed. Program check for each PLC model
Check for all instructions and all operands.
You can see the check result on the "Compile (Program check)" tab of the Output Window.
The left bus-bar on the ladder section window turns red if there is an error in the rung.
• Program check conducted by users
This section describes the procedure of program check, an example of checking result, and
explanation of error levels.
<Program check for one program (task)>
1. Select the ladder section window or nimonic window to check.
2. Select “Program” – “Compile (Program check)”.
The results of program check will be displayed on the Output Window. Refer to “Results of program
check” on the next page for details.
38