2.3 Detailed Description of the Services
2-23
Auto/Manual Switch
This operation command switches the mode to manual mode or
automatic mode, based on the related information setting. This
command can be accepted in setup area 0 only. An “operation error”
will be generated in the following instances:
When the command is executed in “setup area 1"
When auto/manual switching is disabled (not displayed)
When the Controller is switched to manual mode, the “manual manipu-
lated variable” will be displayed. When the Controller is switched from
manual mode to automatic mode, the operation level’s first parameter
will be displayed. When the Controller is switched to manual mode
while already in manual mode, the command will be completed
normally and the display will not change (the contents will not be
refreshed).
Writing Auto/Manual Status in EEPROM
The write mode determines whether the auto/manual status is written
to EEPROM.
Note: When the auto/manual mode is switched with an operation
command through communications and the Controller is in RAM
write mode, the auto/manual status is not stored in EEPROM.
Consequently, if the Controller is restarted by performing a
software reset or turning the power OFF and ON again, the auto/
manual mode is set to the last saved status.
Switching to Manual Mode during Auto-tuning
If the mode is switched during auto-tuning (AT), the AT will be
cancelled and the Controller will be switched to manual mode.
Parameter Initialization
The present settings are returned to the default values and written to
EEPROM. This command can be accepted in setup area 1 only. When
this command is issued in setup area 0, an “operation error” will be
generated.
Alarm Latch Cancel
Write mode Description
Backup mode When the auto/manual mode is switched by
communications, the auto/manual status is writ-
ten to EEPROM.
RAM write mode When the auto/manual mode is switched by
communications, the auto/manual status is not
written to EEPROM.
The status can be written with the Controller
key operation.

Table of Contents

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals